9Programming Instructions Important: The Catalyst Monitor must first be programmed prior to operation. When initially powering up the unit, the dis
10A description of each menu item follows: “Run Signal” There are (3) run types available. The definitions are as follows: None: No run indicati
11”Calibration” Select the channel number to configure by pressing the up / down arrows and pressing the right arrow to select and continue. Th
12“Communication” This allows configuration for downloading data and Modbus communications. ”Data Logging” The setup for EPA required logging of
13Select “A Value” on the next screen and press the arrow. On the following screen, select an RPM value that will indicate engine runni
14Pressing the escape key two times will escape to the normal monitoring mode. “System” “Display defaults” allows the selection of either sing
15Alarm Outputs The Catalyst Monitor will alarm when channel values or differential values are above or below limits as specified. Alarms can be
16Downloading logged values to PC using LogReader software The hardware connection from the Catalyst Monitor to a PC is via a USB cable a
17There are (3) reports generated by the LogReader software: The report named “CatalystDataLog” is a spreadsheet of logged values as configured in t
18The 2nd report named “CatalystDataLogEPAInstant” contains the instantaneous catalyst inlet temperatures taken at 15 minute intervals. Note tha
1IMPORTANT - PLEASE READ BEFORE PROCEEDING! This manual applies to all Version2 Catalyst Monitors. The Dynalco Catalyst Monitor is designed for rel
19Modbus Communication The unit also provides access to the internal registered values using the Modbus Protocol. The diagram below sh
20Modbus Address Registers: The Modbus address registers are defined in the tables below. Input Register Table (table 1) Modicon Address Modbus Of
21300017 16 Channel 5 High Alarm Limit -32768 32767 16 bit signed integer 300018 17 Channel 6 High Alarm Limit -32768 32767 16 bit signed integer 330
22301046-301049 1045-1048 Log Buffer Entry #12 Custom (See table 4) 301050-301053 1049-1052 Log Buffer Entry #13 Custom (See table 4) 301054-
23302006-302007 2005-2006 Channel 3 Float Value -9999.0 99999.0 32 bit Float(IEEE 754) 302008-302009 2007-2008 Channel 4 Float Value -9999.0 99999.0
24302048-302049 2047-2048 Channel 6 High Low Limit -9999.0 99999.0 32 bit Float(IEEE 754) 302050-302051 2049-2050 Channel 1 and 2 Differential Low Al
25
2System Overview The Dynalco Catalyst Monitor is designed to address the EPA mandate regarding continuous monitoring of catalyst inlet temperatu
3Flash Memory: The onboard flash memory is sufficient to hold up to 500,000 data values with date / time stamp. When the Catalyst
4User Interface The Catalyst Monitor is configured via the keypad on the front panel which includes a graphical backlit LCD display
5The Catalyst Monitor has integral mounting clips for securing into the panel. The following drawings illustrate the mounting procedure.
6Terminal Connections All connections are made via the removable connectors on the back of the unit. PIN Description PIN Description 1 GND (P