6.7.8 System Limit
Go to <Configuration>, <System Limits>.
Every System Limit has the same 5 logic inputs: Sensor 1, Sensor 2, Math function, Binary input 1, Binary
input 2. A hysteresis may be applied to the first 3. Each may be inverted or selected to form part of a logical
combination or disabled. The logical combination of inputs may be OR or AND.
Sensor alarm may be additionally combined OR with the System Limit result.
Sensor 1:
Limit low: 0.01 … 200.0 … 999,999
Limit high: 0.01 … 300.0 … 999,999
Sensor 2
Limit low: 0.01 … 400.0 … 999,999
Limit high: 0.01 … 500.0 … 999,999
Math Function
Limit low: -999,999 … 50.0 … 999,999
Limit high: -999,999 … 100.0 … 999,999
Inversion:
Sensor 1: Over speed / Under speed
Sensor 2: Over speed / Under speed
Math: Over-run / Under-run
Binary input 1: active / inactive
Binary input 2: active / inactive
Inclusion in logical combination:
Sensor 1: On / Off System Limit 1
Sensor 2: On / Off System Limit 2
Math: On / Off System Limit 3
Binary input 1: On / Off System Limit 4
Binary input 2: On / Off System Limit 4
Logical combination:
Combined OR / AND
Hysteresis
Hysteresis may be definined for the first 3 inputs via upper and lower limits. If the lower limit is set higher than
the upper limit, the hysteresis is inverted.
Inversion
Every input may be inverted.
Logical combination
The box must be ticked to include the input in the logical combination.
Sensor Alarm
To OR Sensor alarm with the System Limit result the box must be ticked.