3690 NW 53rd Street • Fort Lauderdale, FL 33309 • Ph 954-739-4300 • Fax 954-486-4968 • www.dynalco.com SWT-2000 Frequency Measurement

Seite 2 - TABLE OF CONTENTS

Operating Instructions SWT-2000 DYNALCO 6 Mode 20.5201240ModeOutputValue 0...20mA 4...20mA Startvalue Endvalue [mA] 212Fe hlerlevel4 … 20 mA

Seite 3

Operating Instructions SWT-2000 DYNALCO 7 Reaction time Effective Measurement interval + max 6 ms Contact resistance 50 mΩ Max. (Initial cont

Seite 4

Operating Instructions SWT-2000 DYNALCO 8 3. Principle of Operation 3.1 General The model SWT-2000 is microprocessor controlled and operates

Seite 5 - 1. Product Features

Operating Instructions SWT-2000 DYNALCO 9 4. Installation The SWT-2000 may only be installed by competent personnel. Only undamaged and corr

Seite 6 - 2. Specifications

Operating Instructions SWT-2000 DYNALCO 10 5.1.2 Terminal A Supply + : Input Supply (+) - : Input Supply (-) : Earth Binary Inputs

Seite 7 - NOT O.K

Operating Instructions SWT-2000 DYNALCO 11 5.1.3 Terminal B Open Collector Outputs Oc1 / Oc2 OC1+ : positive Open Collector 1 (Emitter)

Seite 8

Operating Instructions SWT-2000 DYNALCO 12 6. Configuration via PC Software 6.1 Software Concept The SWT-2000 Ethernet connection is used to

Seite 9 - 2.4 Outputs

Operating Instructions SWT-2000 DYNALCO 13 6.4 Configuration Software Configuration User and Process User SWT-2000 parameters are divided in

Seite 10 - 2.4.2 Relays Outputs

Operating Instructions SWT-2000 DYNALCO 14 6.5.2 …resetting to factory default To reset parameters to factory settings go to <Settings>

Seite 11 - 2.6 Environment

Operating Instructions SWT-2000 DYNALCO 15 6.6.3 Writing a Configuration to the SWT-2000 When a new configuration file is ready it can be do

Seite 12 - 3. Principle of Operation

TABLE OF CONTENTS 1. Product Features 1 2. Specifications 2 2.1 General 2 2.2 Inputs 2 2.2.1 Sensor Inputs 2 2.3 Binary Inp

Seite 13 - 5. Connections

Operating Instructions SWT-2000 DYNALCO 16 6.7.2 Binary Input Configuration To configure binary inputs go to <Configuration>, <Bina

Seite 14 - - : Input Supply (-)

Operating Instructions SWT-2000 DYNALCO 17 6.7.5 Machine Factor Go to <Configuration>, <System>. The Machine factor establishes

Seite 15 - 5.1.3 Terminal B

Operating Instructions SWT-2000 DYNALCO 18 6.7.7 Math Function Go to <Configuration>, <Math>. Math function is an additional i

Seite 16 - 6.2 PC Settings

Operating Instructions SWT-2000 DYNALCO 19 6.7.8 System Limit Go to <Configuration>, <System Limits>. Every System Limit has th

Seite 17 - 6.5 Configuration File

Operating Instructions SWT-2000 DYNALCO 20 6.7.9 Relay Outputs To configure relay outputs go to <Configuration>, <Relay / Open Coll

Seite 18

Operating Instructions SWT-2000 DYNALCO 21 Defines whether an Open Collector state should be held until reset. Safety Function Defines whe

Seite 19 - 6.7 Configuring

Operating Instructions SWT-2000 DYNALCO 22 6.7.12 Copy Parameter Set Go to <Configuration>, <Copy from Control A>. A Parameter

Seite 20 - 6.7.4 Sensor Alarm

Operating Instructions SWT-2000 DYNALCO 23 6.8.2 Changing the Password Go to <Settings>, <Change Config user password> or <Ch

Seite 21 - 6.7.6 Dynamic Error

Operating Instructions SWT-2000 DYNALCO 24 7. Operating Behavior 7.1 Power On The parameter set e.g. as defined by binary inputs is immediat

Seite 22 - 6.7.7 Math Function

Operating Instructions SWT-2000 DYNALCO 25 7.2 Frequency Measurement Every frequency measurement starts with the negative edge of the input

Seite 23 - 6.7.8 System Limit

7.2.2 Signal Failure 26 7.3 Functions 26 7.3.1 "FUNC" Push Button 26 7.3.2 Parameter Sets A, B, C and D 26 7.

Seite 24 - 6.7.9 Relay Outputs

Operating Instructions SWT-2000 DYNALCO 26 7.2.2 Signal Failure Signal failure is defined as the sudden transition from an input frequency t

Seite 25 - 6.7.11 Analog Output

Operating Instructions SWT-2000 DYNALCO 27 7.3.4 Math Function To set a Math function on a speed input please follow the steps below. (Exam

Seite 26 - 6.8 Settings

Operating Instructions SWT-2000 DYNALCO 28 7.3.5 Frequency X2 and X4 Prerequisites for the X2 and X4 function are that the input frequencies

Seite 27 - 6.9 Info

Operating Instructions SWT-2000 DYNALCO 29 7.3.8 Interpretation of System Limit Inputs Upper and lower set points may be set for each of the

Seite 28 - 7. Operating Behavior

Operating Instructions SWT-2000 DYNALCO 30 8. Mechanical Construction / Housing Dimensions 8.2 Mounting Wall mounting Top hat rail mo

Seite 29 - 7.2 Frequency Measurement

Operating Instructions SWT-2000 DYNALCO 31 9. Accessories Interface Cable PC – SWT-2000 (6 Ft crossover): Part No. 270A-105039

Seite 31 - 7.3.4 Math Function

Operating Instructions SWT-2000 DYNALCO 1 1. Product Features The model SWT-2000 measures and monitors frequency signals (speed proportional

Seite 32 - 7.3.7 Analog Output

Operating Instructions SWT-2000 DYNALCO 2 2. Specifications 2.1 General Measurement time 2ms / 5ms / 10ms / 20ms / 50ms / 100ms / 200ms /

Seite 33 - 7.5 Power Failure

Operating Instructions SWT-2000 DYNALCO 3 Input signal for fixed 3V trigger (+/-15%) • Max. Voltage: 80VRMS (226Vpp) • Best suited to digita

Seite 34 - 8.2 Mounting

Operating Instructions SWT-2000 DYNALCO 4 Input signal for adaptive trigger min. 500mVpp (+/-10%) 180mVRMS • Max. Voltage: 80VRMS (226Vpp) •

Seite 35 - 9. Accessories

Operating Instructions SWT-2000 DYNALCO 5 Sensor monitoring 3 sensor monitoring settings are available in the configuration software: • No